Compact wastewater treatment
Overview
Our compact wastewater treatment system “WaterPaq” combines high performance and low operational expenses on a remarkably small footprint.
Containerized APATEQ wastewater treatment plants can handle from 10 m³/day up to 120 m³/day. Depending on the plant capacity, the process technology is housed into one or two ISO containers.
read more
Effluent from the APATEQ “WaterPaq” complies with the toughest international regulations for direct discharge. Alternatively the container can be customized in order to produce water for re-use purposes, such as washing, cooling or irrigation.
The “WaterPaq” is ideally suited for operation at remote locations, even in environmentally sensitive landscapes such as environmental protection zones. Operators of our system benefit from the following key features:
- Savings of discharge fees/ fresh water expenses
- Ideally suited for high total suspended and dissolved solids (TSS and TDS)
- Service is flexible with regard to fluctuations to inlet volume as well as TDS and TSS
- Easily scalable technology
- Skid mounted and/or containerized solution for mobile use (CSC certified shippable containers)
- Eliminates bacteria and most of the viruses
- The membranes are positioned outside of the bioreactor for ease of handling and serviceability
- Small footprint
- Suitable for harsh climate environments due to specific insulation: operational at temperatures between -45°C and +50°C
- Remote operation, surveillance and troubleshooting
- Short lead time
- Quick commissioning (1 week only) and fast start-up time due to cross-flow membranes
Technical Specifications
WaterPaq 10 | WaterPaq 25 | WaterPaq 60 | WaterPaq 120 | |
Water treatment capacity | 2 – 10 m³ / day(530 – 2649 GPD or 10 – 50 PE) | 5 – 25 m³ / day(1320 – 6600 GPD or 25 – 125 PE) | 12 – 60 m³ / day(3170 – 15850 GPD or 60 – 300 PE) | 24 – 120 m³ / day(6340 – 31700 GPD or 120 – 600 PE) |
Buffer tank capacity (8h) | 3 m³ | 8.3 m³ | 20 m³ | 40 m³ | Container size / type | 20’ HC (optional) | 20’ HC | 40’ HC | 2 × 40‘ HC |
Weight (empty / dry) | approx. 3t (w/o ctnr.) | approx. 6t | approx. 11t | approx. 11t + 13t |
Membrane filtration capability | 40 nm(ultrafiltration) | 40 nm(ultrafiltration) | 40 nm(ultrafiltration) | 40 nm(ultrafiltration) |
Energy requirement (without heaters or AC equipment) | approx. 4 kWh | approx. 5 kWh | approx. 8 kWh | approx. 13 kWh |
Operating environmental temperature | - 45°C to + 50°C | - 45°C to + 50°C | - 45°C to + 50°C | - 45°C to + 50°C |
Ambient temperature inside plant during operation | + 15°C to + 30°C | + 15°C to + 30°C | + 15°C to + 30°C | + 15°C to + 30°C |
Noise emission | max. 65 dB (A) | max. 65 dB (A) | max. 65 dB (A) | max. 65 dB (A) |
Treated sludge dry solids (DS) contents | min. 15% (typ. 17%) | min. 15% (typ. 17%) | min. 15% (typ. 17%) | min. 15% (typ. 17%) |
Influent wastewater characteristics (assumed): | Effluent water characteristics: | |||
BOD5 | 100 – 400 mg/l | < 5 mg/l | ||
Total Suspended Solids (TSS) | 100 – 350 mg/l | < 1 mg/l | ||
Total Kjeldahl Nitrogen (TKN) | 15 – 45 mg/l | < 2 mg/l | ||
Faecal Coliforms | - | < 1 | ||
Virus Retention | - | 99.99% | ||
Turbidity | - | < 1 NTU | ||
Ph value | - | ~ 6 – 8.5 |
WaterPaq 10 | WaterPaq 25 | |
Water treatment capacity | 2 – 10 m³ / day(530 – 2649 GPD or 10 – 50 PE) | 5 – 25 m³ / day(1320 – 6600 GPD or 25 – 125 PE) |
Buffer tank capacity (8h) | 3 m³ | 8.3 m³ | Container size / type | 20’ HC (optional) | 20’ HC |
Weight (empty / dry) | approx. 3t (w/o ctnr.) | approx. 6t |
Membrane filtration capability | 40 nm(ultrafiltration) | 40 nm(ultrafiltration) |
Energy requirement (without heaters or AC equipment) | approx. 4 kWh | approx. 5 kWh |
Operating environmental temperature | - 45°C to + 50°C | - 45°C to + 50°C |
Ambient temperature inside plant during operation | + 15°C to + 30°C | + 15°C to + 30°C |
Noise emission | max. 65 dB (A) | max. 65 dB (A) |
Treated sludge dry solids (DS) contents | min. 15% (typ. 17%) | min. 15% (typ. 17%) |
WaterPaq 60 | WaterPaq 120 | |
Water treatment capacity | 12 – 60 m³ / day(3170 – 15850 GPD or 60 – 300 PE) | 24 – 120 m³ / day(6340 – 31700 GPD or 120 – 600 PE) |
Buffer tank capacity (8h) | 20 m³ | 40 m³ | Container size / type | 40’ HC | 2 × 40‘ HC |
Weight (empty / dry) | approx. 11t | approx. 11t + 13t |
Membrane filtration capability | 40 nm(ultrafiltration) | 40 nm(ultrafiltration) |
Energy requirement (without heaters or AC equipment) | approx. 8 kWh | approx. 13 kWh |
Operating environmental temperature | - 45°C to + 50°C | - 45°C to + 50°C |
Ambient temperature inside plant during operation | + 15°C to + 30°C | + 15°C to + 30°C |
Noise emission | max. 65 dB (A) | max. 65 dB (A) |
Treated sludge dry solids (DS) contents | min. 15% (typ. 17%) | min. 15% (typ. 17%) |
Influent wastewater characteristics (assumed): | Effluent water characteristics: | |
BOD5 | 100 – 400 mg/l | < 5 mg/l |
Total Suspended Solids (TSS) | 100 – 350 mg/l | < 1 mg/l |
Total Kjeldahl Nitrogen (TKN) | 15 – 45 mg/l | < 2 mg/l |
Faecal Coliforms | - | < 1 |
Virus Retention | - | 99.99% |
Turbidity | - | < 1 NTU |